A first-pass battery and generator size for the loads you need through an outage.

Battery, usable

5.7kWh

For 12 hours, get a battery of about 7.1 kWh (5.7 kWh you can use). Or get a generator of at least 5.0 kW.

NREL REopt

Self-checked · The spec's 9.6 kWh load list, 60 kWh usable and 75 kWh nameplate at 12 hours, and 7.0 kW generator with motor start pass, each hand-computed. What this means

A first-pass size to take to an installer, not a design. · Self-checked only: no independent check has been run yet · Example values · Review pending Report a problem

Report a problem

Your county's outage history

Your ZIP finds your county. Its recorded outages from EAGLE-I set the outage length, and the battery for each length is shown.

One load a line: its name, running kW, and hours a day, and optionally when it starts, as "lights, 0.3 kW, 6 h, from 18:00".

More options

How we got this

Method

Battery usable kWh = critical energy over the outage, starting at the hour with the most critical load; nameplate = usable ÷ usable share. Generator kW = peak critical kW − the largest motor's running kW + its starting kW.

Steps

  1. Daily critical energy: refrigerator 0.2 kW × 24 h = 4.8 kWh; well pump 1.5 kW × 2 h = 3 kWh; lights 0.3 kW × 6 h = 1.8 kWh; total 9.6 kWh.
  2. Critical load by hour: 0.33, 0.33, 0.33, 0.33, 0.33, 0.33, 0.33, 0.33, 0.33, 0.33, 0.33, 0.33, 0.33, 0.33, 0.33, 0.33, 0.33, 0.33, 0.63, 0.63, 0.63, 0.63, 0.63, 0.63 kW (midnight to 11 pm). A load with no start time is spread over the day.
  3. Battery: the outage starts at 18:00, the hour with the most critical load, and lasts 12 hours: 5.7 kWh usable ÷ 80% usable window = 7.13 kWh nameplate.
  4. Generator: 2 kW − 1.5 kW running + 4.5 kW starting = 5 kW. A load with no start time counts at its full kW, since it could run at any moment.
  5. Generator ratings are usually stated at 0.8 power factor. Check motor starting against the generator's own motor-starting data; no starting multiplier is assumed.

Assumptions

  • Loads with no start time are spread evenly over the day for the battery, and counted at full kW for the generator.
  • No inverter losses, battery aging, or temperature derating.

Sources

Known limits

  • County outage history means some customers in the county were out, not this address; durations are a typical guide, not a worst case.
  • No inverter losses, battery aging, or temperature derating.