Methods: Transformer sizing and loading

calc.transformer.size · Version 0.1.0

Method

Apparent power is √3 × V line-to-line × A ÷ 1,000 for three-phase service and V × A ÷ 1,000 for single-phase, or kW ÷ power factor. Loading is kVA ÷ rating, and headroom is rating − kVA.

Assumptions

Sources

Worked examples

ExampleIndependent sourceToleranceLast result
600 A at 480 V three-phase on a 500 kVA transformercalc/transformer-sizing spec, scenario "Three-phase from amps": √3 × 480 × 600 ÷ 1,000±0.05, ±0.05Passed on Oct 31, 2026
A 412 kW peak at 0.95 on a 500 kVA transformercalc/transformer-sizing spec, scenario "Peak loading"±0.05, ±0.05, ±0.05Passed on Oct 31, 2026
200 A at 240 V single-phaseHand computation: 240 × 200 ÷ 1,000±0.05Passed on Oct 31, 2026

Known differences from reference engines

None recorded.