Methods: Power factor correction

calc.power-factor.correct · Version 0.1.0

Method

Correction in kVAR is kW × (tan(arccos(PF now)) − tan(arccos(PF target))); apparent power is kW ÷ PF; line current is kVA × 1,000 ÷ (√3 × V) for three-phase service. On a tariff that bills demand scaled to a power-factor threshold, billing kW is kW × threshold ÷ PF when PF is lower.

Assumptions

Sources

Worked examples

ExampleIndependent sourceToleranceLast result
500 kW at 0.78, corrected to 0.95calc/power-factor-correction spec, scenarios "Correcting 0.78 to 0.95" and "Billing-demand adjustment removed"±0.05, ±0.05, ±0.05, ±0.01Passed on Oct 31, 2026
DOE example: 100 kW and 100 kVAR, to 0.95DOE "Reducing Power Factor Cost": a 67 kVAR capacitor±1Passed on Oct 31, 2026
WSU and NEEA example: 100 kW at 0.70, to 0.95WSU and NEEA factsheet, Figure 4: a 69 kVAR capacitor±1Passed on Oct 31, 2026

Known differences from reference engines

None recorded.