Methods: Overhead conductor ampacity

calc.line-rating.ampacity · Version 0.1.0

Method

At the maximum conductor temperature, the steady-state current is √((convective cooling + radiated heat loss − solar heat gain) ÷ AC resistance), following the IEEE 738-2023 heat balance: forced convection by the larger of its low- and high-wind correlations with the wind-angle factor, or natural convection if larger; radiation from emissivity and the temperatures; clear-sky solar gain from the sun's position, elevation, and line bearing; and resistance interpolated between the two values entered.

Assumptions

Sources

Worked examples

ExampleIndependent sourceToleranceLast result
A 1.108 in conductor at 40 °C in 2 ft/s windThis tool's own heat balance for these inputs; the method is checked against linerate's 50 stored cases±0.5, ±0.05Passed on Oct 31, 2026

Known differences from reference engines

None recorded.